TY - JOUR ID - TI - Effect of Mixed Corrosion Inhibitors in Cooling Water System تأثير خليط مثبطات التآكل في منظومة خزان التبريد AU - Dina Raheem دينا رحيم PY - 2011 VL - 7 IS - 4 SP - 76 EP - 87 JO - Al-Khwarizmi Engineering Journal مجلة الخوارزمي الهندسية SN - 18181171 23120789 AB - The effect of mixed corrosion inhibitors in cooling system was evaluated by using carbon steel specimens and weight loss analysis. The carbon steel specimens immersed in mixture of sodium phosphate (Na2 HPO4) used as corrosion inhibitor and sodium glocunate (C6 H11 NaO7) as a scale dispersant at different concentrations (20,40, 60, 80 ppm) and at different temperature (25,50,75 and 100)ºC for (1-5) days. The corrosion inhibitors efficiency was calculated by using uninhibited and inhibited water to give 98.1%. The result of these investigations indicate that the corrosion rate decreases with the increase the corrosion inhibitors concentration at 80 ppm and at 100ºC for 5 days, (i.e, corrosion rate= 0.014gmd).

تم تقييم تأثير خليط مثبطات التآكل في منظومة التبريد باستعمال معدن كربون ستيل وطريقة فقدان الوزن . غمرت نماذج الكربون ستيل في خليط من فوسفات الصوديوم Na2HPO4 كمثبط تأكل وكلوكنيت الصوديوم C6H11NaO7 كمشتت تكلسات وبتراكيز مختلفة (20,40,60,80) جزء بالمليون وعند درجة حرارة مختلفة ,(25,50,75,100) ◦م و لمدة (1-5) أيام . تم حساب كفاءة المثبطات باستخدام ماء بدون إضافات ومع الإضافات وكانت كفاءة الخليط98.1% عند تركيز80 جزء بالمليون. نتائج البحث تبين أن معدل التآكل يقل مع زيادة تركيز خليط مثبط التآكل عند تركيز 80 جزء بالمليون ودرجة حرارة100◦م ولمدة 5 أيام, أي إن معدل التآكل =0.014 غم /م٢. يوم . ER -