TY - JOUR ID - TI - Dynamics and Control of Double-Pipe Heat Exchanger دراسة ديناميكية المبادل الحراري دو الانبوب المزدوج والسيطرة علية AU - Dr.Khalid.M.Mousa د.خالد مخلف موسى PY - 2010 VL - 13 IS - 2 SP - 129 EP - 140 JO - Al-Nahrain Journal for Engineering Sciences مجلة النهرين للعلوم الهندسية SN - 25219154 25219162 AB - Experimental investigation was conducted to study the dynamics of double-pipe heat exchanger using step change in flow rate of hot water and observe its effect on the temperature of cold water and it was found that the transfer function can be represented by first order system plus dead time (FOPDT). MATLAB 7.4 simulation and programming was used to show the response of close-loop system using P, PI, PID and fuzzy logic control. The Smith predictor was used to remove the effect of transport delay on the process and it was found that this method greatly improve the response of the system. The stability of the overall closed loop system was proved by using Bod plot diagram.

لقد تم اجراء تجارب عملية لايجاد ديناميكية المبادل الحراري من نوع الانبوب المزدوج عن طريق اجراء اضطراب تدريجي في معدل جريان الماء الحار و ملاحظة التغير الحاصل في درجة حرارة الماء البارد الخارج للمبادل الحراري وقد وجد بانه يمكن تمثيل النظام بدالة تحويل من الدرجة الاولى مع تعويق زمني. تم محاكات النظام عن طريق استخدام برنامج MATLAB لغرض دراسة السيطرة على المبادل الحراري وباستخدام طرق مختلفة مثل التناسبي والتناسبي التكاملي والتناسبي التكاملي التفاضلي و السيطرة الضبابية.وقد تم ازالة تاثير التعويق الزمني عن طريق استخدام Smith predictor وظهر تحسن كبير في سلوكية النظام اخيرا تم دراسة استقرارية النظام ووجد بان النظام مستقر. ER -