TY - JOUR ID - TI - Heat Transfer and Fluid Flow Characteristic in banks Flat Tubes انتقال الحرارة وجريان مائع لحزمة من الأنابيب المستوية AU - Amer Jameel Shareef Abdulmajeed A. Ramadhan PY - 2011 VL - 18 IS - 4 SP - 88 EP - 103 JO - Tikrit Journal of Engineering Sciences مجلة تكريت للعلوم الهندسية SN - 1813162X 23127589 AB - In this research a study effect of the length ratio (L/Da) and the height ratio (H/Da) for banks flat tube heat exchanger In-Line and staggered arrangement on force convection heat transfer and friction coefficient by (Fluent-CFD) numerical program. The governing equations (mass, momentum and energy) are solving by using Finite Volume (Fluent-CFD) software for considering steady state, two dimensional, at constant heat flux with Reynold’s number (100≤Re≤8000). The results show that increasing (H/Da), (L/Da) lead to decreasing friction coefficient and enhancement of (Nu) is at (H/Da=2) for all (L/Da) values In-line arrangement and at (H/Da =2, L/Da =5) for staggered arrangement.

تضمن البحث دراسة تأثير النسبة الباعية الطولية (L/Da) والشاقولية (H/Da) لمبادل حراري ذو الانابيب المسطحة في ترتيب خطي ومتخالف لانتقال الحرارة بالحمل القسري ومعامل الاحتكال السطحي بأستخدام البرنامج العددي(Fluent-CFD). تم حل المعادلات الحاكمة (معادلة الاستمرارية والزخم والطاقة) بطريقة الحجوم المحددة بواسطة البرنامج المذكوراعلاه مع الاخذ بنظر الاعتبار ان الجريان ثنائي البعد للحالة المستقرة عند ثبوت الفيض الحراري لانابيب المبادل لمدى عدد رينولد(100≤Re≤8000).اظهرت النتائج ان زيادة (H/Da)و(L/Da) يؤدي الى انخفاض في قيمة معامل الاحتكاك السطحي, كما ان افضل قيمة لعدد نسلت عند(H/Da=2) لجميع قيم (L/Da) للترتيب الخطي واما للترتيب المتخالف (H/Da =2 ,L/Da =5) ER -