TY - JOUR ID - TI - ELECTRICAL STRESS CONCENTRATION AT THE TERMINALS OF M.V. & H.V. XLPE CABLES تركيز الاجهادات الكهربائية عند منطقة الاطراف لقابلوات البولي اثيلين متقاطع الاواصر ذوات الفولتية المتوسطة و العالية AU - Farook kh. Amori أ. فاروق خليل عموري AU - Saad Samuel Sheet سعد صاموئيل شيت PY - 2006 VL - 14 IS - 1 SP - 39 EP - 46 JO - AL-Rafidain Engineering Journal (AREJ) مجلة هندسة الرافدين SN - 18130526 22201270 AB - AbstractLongitudinal and radial stresses in a M.V. and H.V. cables through terminalsare computed using Schwarz Christoffel transformation for field sketching.The terminals and associated cable are rated at 11KV, 33KV and 132KV a.cinsulated by cross–linked polyethylene (XLPE). The electrical field sketching at thecable terminations is carried out theoretically and the results are confirmed byexperiments.It seems that the maximum stresses occurs in the cable insulation and themaximum longitudinal stresses along the screened outer surface of the cross-linkedpolyethylene (XLPE) insulation occurs between the cable and the termination center.The results show that the maximum longitudinal stress is many times theoncorrespding maximum radial values.Key Words: Stress distribution for XLPE cable, Termination of XLPE cables

منطقة الأطرافباستخدام تحويلة شوارتز كرستوفل الخاصة لرسم المجال الكهربائي .إن أطراف القابلوات كانت بمقننات 11 كيلو فولت ، 33 كيلو فولت و 132 كيلو فولت بفولتية متناوبةو ذوات عوازل البولي اثيلين متقاطع الأواصر ، تم رسم المجال الكهربائي لأطراف القابلوات بالطريقة النظرية وتم تأكيد من صحة النتائج النظرية عن طريق النتائج العملية المبينة .من النتائج العملية و النظرية يمكن القول بان اعظم إجهاد يحدث في عازل القابلو وان اعظم إجهاد طولييحدث عند السطح الخارجي لطبقة الشبه موصل الداخلية الفاصلة بين الموصل و عازل البولي اثيلين متقاطعالأواصر .و من النتائج المبينة بالتحليل النظري و كذلك من الجزء العملي يمكن القول بان اعظم إجهاد طولي يكونعادة عدة أضعاف من قيمة اعظم إجهاد قطري . ER -