TY - JOUR ID - TI - Experimental Study of the effect of closed cavity wall on buildings cooling loads saving دراسة عملية لتأثير الجدار ذي التجويف الهوائي المغلق في تخفيض احمال تبريد الابنية AU - Qussai Jihad Abdul Ghafour قصي جهاد عبد الغفور AU - Bashar Kamil Mahmoud بشار كامل محمود PY - 2015 VL - 21 IS - 1 SP - 1 EP - 12 JO - Journal of Engineering مجلة الهندسة SN - 17264073 25203339 AB - The experimental study showed the use of closed cavity wall (the thickness of the cavity 5cm) made a percentage reduction in the cooling load caused by heat gain from the wall by (21.5 %) compared with the conventional wall. also the thermal resistance of the closed cavity was an average (0.2 m2.oC/W). The experimental results of the study showed that the use of closed cavity wall reduced the average temperature of the inner surface of the wall during the day, and that the reduction was an average (0.45 oC) when compared with the conventional wall , as well as the use of closed cavity wall reduced the temperature difference range of the inner surface of the wall during the day, and that the reduction was an average (0.66 oC) when compared with the conventional wall .

أظهرت الدراسة العملية ان استخدام جدار ذي تجويف هوائي مغلق (سمك التجويف 5cm) يعمل على خفض حمل الكسب الحراري عبر الجدار بنسبة (21.5 %) بالمقارنة مع جدار تقليدي (بدون تجويف). وبينت النتائج ايضاً أن المقاومة الحرارية للتجويف المغلق كانت بمعدل (0.2 m2.oC/W). وأظهرت النتائج العملية للدراسة أن الجدار ذي التجويف الهوائي المغلق يعمل على خفض متوسط درجة حرارة السطح الداخلي للجدار خلال اليوم بمعدل (0.45 oC) مقارنة مع الجدار (بدون تجويف). وكذلك خفض مدى التغير في درجة الحرارة للسطح الداخلي للجدار خلال اليوم بمعدل (0.66 oC) مقارنة مع الجدار (بدون تجويف) ايضاً. ER -