TY - JOUR ID - TI - Experimental Performance of a Finned-tube Silica Gel Adsorption Chiller for Air-Conditioning Application الأداء التجريبي لمبرد امتزازي ذو انبوب زعنفي للسيلكا جل لاغراض تبريد الهواء AU - Mohammed A. Atiya AU - Farkad A. Lattieff فرقذ علي لطيف AU - Adil A. Al-Hemiri عادل احمدعوض PY - 2014 VL - 10 IS - 3 SP - 68 EP - 77 JO - Al-Khwarizmi Engineering Journal مجلة الخوارزمي الهندسية SN - 18181171 23120789 AB - This work presents the construction of a test apparatus for air-conditioning application that is flexible in changing a scaled down adsorbent bed modules. To improve the heat and mass transfer performance of the adsorbent bed, a finned-tube of the adsorbent bed heat exchanger was used. The results show that the specific cooling power (SCP) and the coefficient of performance (COP) are 163 W/kg and 0.16, respectively, when the cycle time is 40 min, the hot water temperature is 90oC, the cooling water temperature is 30oC and the evaporative water temperature is 11.4oC.

يعرض هذا البحث بناء جهاز اختبار لمنظومة تبريد الهواء يتسم بالمرونة في تغيير موديل وحدة الامتزاز. فمن اجل تحسين كفاءة انتقال الحرارة والمادة، تم استخدام مبادل حراري مزود بزعانف لوحدة الامتزاز . أظهرت النتائج أن سعة التبريد (SCP) ومعامل الأداء (COP) هي 163 واط / كجم و 0.16، على التوالي، عندما يكون وقت الدورة هو 40 دقيقة، ودرجة حرارة الماء الساخن 90 درجة مئوية،ودرجة حرارة مياه التبريد 30 درجة مئوية ودرجة حرارة الماء المبرد 11.4 درجة مئوية. ER -