Fulltext

Method for Shielding the Magnetic Field Generated in a 132/33/11(6.6)KV Baghdad Indoor Distribution Substation

طریقة للحمایة من المجال المغناطیسي المتولد في داخل محطة توزیع ثانویة 132/33/11 (6.6)kV في بغداد

Suad I. Shahl

Engineering and Technology Journal مجلة الهندسة والتكنولوجيا
ISSN: 16816900 24120758 Year: 2012 Volume: 30 Issue: 15 Pages: 2562-2576
Publisher: University of Technology الجامعة التكنولوجية

Abstract

This research introduces the study carried out on one of Baghdad East 132/33/11(6.6) kV distribution substations to mitigate 50Hz magnetic field of indoor distribution substation under normal operation. Shielding was performed at the power sources such as busbars rather than at the affected areas. Three-dimensional finite element method (FEM) is used to calculate the magnetic field density in the space nearby the busbars so as to analyze the shielding effectiveness of an eddy current shield applied to a 132/33/11(6.6)kV substation. It also deals with the influence of shield distance from busbar, thickness and material of shield on the eddy current losses and shielding efficiency applied to 3D finite element model of a particular busbar configuration.

يقدم هذا البحث دراسة نفذت على احدى محطات التوزيع الثانوية 133/33/11(6.6)kV في شرق بغداد للتخفيف من المجال المغناطيسي ذي التردد (50Hz) داخل محطة التوزيع ثانوية تحت ظروف التشغيل الطبيعي. نفذت الحماية عند مصادر الطاقة مثل القضبان العمومية بدلا من المناطق المتأثرة. استخدمت طريقة العنصر المحدود ثلاثية الابعاد في حساب كثافة المجال المغناطيسي في الفضاء القريب من القضبان العمومية لكي نحلل فعالية درع وقاية التيارات الدوامة المسلط على المحطة الثانوية .133/33/11(6.6)kV حيث يتعامل هذا البحث مع تأثير المسافة بين الدرع الواقي و القضيب العمومي, سمك ومادة معدن الدرع الواقي على خسائر التيار الدوام وكذلك كفاءة الحماية لترتيب معين لقضيب عمومي بأعتماد نموذج ثلاثي الابعاد للعنصر المحدود.

Keywords

Magnetic fields --- Eddy current --- Finite Element Method --- FEM --- shielding --- Substation