Electromagnetic Interference Caused by Iraqi 400kV Transmission Lines on Buried Oil Pipelines
التداخلات الكھرومغناطیسیة المتسببة بواسطة خطوط نقل الطاقة العراقیة 400kv على خطوط انابیب النفط المدفونة

Author: Suad I. Shahl
Journal: Engineering and Technology Journal مجلة الهندسة والتكنولوجيا ISSN: 16816900 24120758 Year: 2010 Volume: 28 Issue: 24 Pages: 6937-6953
Publisher: University of Technology الجامعة التكنولوجية

Loading...
Loading...
Abstract

The electromagnetic interference caused by power transmission lines to oil and gas buried pipelines is under investigation for many years. Especially during fault conditions, large currents and voltages are induced on the pipelines that may pose danger to working personnel or may accelerate the corrosion of the pipelin’es metal. In this research, the Joule effect of eddy currents induced in the oil buriedpipelines due to the magnetic fields produced by nearby 400kV transmission lines in the South of Iraq have been computed. A computational model based on 2D finite element approach to calculate the heat generation rate. The influence of different earth resistivities for homogeneous earth model during steady state andfault conditions is analyzed. A mitigation system using mitigation wires has been simulated to reduce induced eddy current heating effects to the safety limit.

تخضع التداخلات الكهرومغناطيسية المتولدة من خطوط نقل الطاقة على خطوط انابيب النفط والغاز والممتدة تحت الارض للبحث منذ عدة سنوات. خصوصا اثناء ظروف الاعطال حيث تتسبب هذه التداخلات في توليد تيارات وفولتيات كبيرة مستحثة على خطوط الانابيب التي قد تشكل خطر لتشغيل العاملين او قد تعجل من تآكل معدن خط الأنابيب. سيتم في هذا البحث حساب الأثر الحراري للتيارات الدوامية المحتثة بسبب المجالات المغناطيسية المتولدة من 400 في جنوب العراق على خطوط انابيب النفط القريبة والممتدة Vk خطوط نقل الطاقة ذاتتحت الارض. لقد استخدم نموذج حسابي مستند على نظرية العنصر المحدود ثنائي البعد في حساب المعدل الحراري المتولد. تم تحليل تأثير مختلف المقاومات النوعية لنموذج متجانس للارض اثناء الظروف العادية وفي حالة وجود عطل.وهذا يتطلب القيام بأجراءات وقائية للحد والتقليل من تأثيرات الأثر الحراري للتيارات الدوامية المحتثة بما يتوافق مع حدود الامان .


Article
Method for Shielding the Magnetic Field Generated in a 132/33/11(6.6)KV Baghdad Indoor Distribution Substation
طریقة للحمایة من المجال المغناطیسي المتولد في داخل محطة توزیع ثانویة 132/33/11 (6.6)kV في بغداد

Author: Suad I. Shahl
Journal: Engineering and Technology Journal مجلة الهندسة والتكنولوجيا ISSN: 16816900 24120758 Year: 2012 Volume: 30 Issue: 15 Pages: 2562-2576
Publisher: University of Technology الجامعة التكنولوجية

Loading...
Loading...
Abstract

This research introduces the study carried out on one of Baghdad East 132/33/11(6.6) kV distribution substations to mitigate 50Hz magnetic field of indoor distribution substation under normal operation. Shielding was performed at the power sources such as busbars rather than at the affected areas. Three-dimensional finite element method (FEM) is used to calculate the magnetic field density in the space nearby the busbars so as to analyze the shielding effectiveness of an eddy current shield applied to a 132/33/11(6.6)kV substation. It also deals with the influence of shield distance from busbar, thickness and material of shield on the eddy current losses and shielding efficiency applied to 3D finite element model of a particular busbar configuration.

يقدم هذا البحث دراسة نفذت على احدى محطات التوزيع الثانوية 133/33/11(6.6)kV في شرق بغداد للتخفيف من المجال المغناطيسي ذي التردد (50Hz) داخل محطة التوزيع ثانوية تحت ظروف التشغيل الطبيعي. نفذت الحماية عند مصادر الطاقة مثل القضبان العمومية بدلا من المناطق المتأثرة. استخدمت طريقة العنصر المحدود ثلاثية الابعاد في حساب كثافة المجال المغناطيسي في الفضاء القريب من القضبان العمومية لكي نحلل فعالية درع وقاية التيارات الدوامة المسلط على المحطة الثانوية .133/33/11(6.6)kV حيث يتعامل هذا البحث مع تأثير المسافة بين الدرع الواقي و القضيب العمومي, سمك ومادة معدن الدرع الواقي على خسائر التيار الدوام وكذلك كفاءة الحماية لترتيب معين لقضيب عمومي بأعتماد نموذج ثلاثي الابعاد للعنصر المحدود.


Article
Application of GIS for the Evaluation of Electromagnetic Field Effects for Iraqi 132KV Electrical Transmission System

Authors: Afaneen A. Alkhazraji --- Suad I. Shahl
Journal: Engineering and Technology Journal مجلة الهندسة والتكنولوجيا ISSN: 16816900 24120758 Year: 2011 Volume: 29 Issue: 9 Pages: 1751-1764
Publisher: University of Technology الجامعة التكنولوجية

Loading...
Loading...
Abstract

This research endeavors to create the 50Hz electromagnetic field atlas forpopulated urban areas in the city of Baghdad (Iraq). For this purpose, the 3-dimensions numerical model based on finite element method (FEM) with timeharmonic system is used for simulated and modeling electric and magnetic fieldssurrounding the 132kV transmission system. The calculated magnetic and electricfield levels are compared to exposure guidelines given by International Commissionon Non-Ionizing Radiation Protection (ICNIRP). To assign the dangers regions in thecity, the properties of the Geographical Information System (GIS) were used. TheGIS map highlighted visually the unsafe zones and facilitate the extraction of theelectric and magnetic field levels of exposure.

Listing 1 - 3 of 3